6

Calibration level

Measured value correction (

CAL)

is only visible if

ConF / InP.1 / Corr = 1

or

2 is chosen.

The measured value can be matched in the calibration menu (

CAL). Two me-

thods are available:

Offset correction

(

ConF/ InP.1 / Corr =1 ):

w possible on-line at the

process

2-point correction

(

ConF/ InP.1 / Corr = 2 ):

w is possible off-line with

process value simulator

Calibration level

KS 90-1 / KS 92-1

61

X

standard setting

offset correction

InL.1

OuL.1

new

display

OuL.1

old

X

standard setting

2-point correction

InL.1

InH.1

OuL.1

new

OuH.1

new

display

OuH.1

old

OuL.1

old

Advertising