8 self-tuning start 21, 9 self-tuning cancellation 21, Cancelation 21 – West Control Solutions KS 92-1 User Manual

Page 21

Advertising
background image

3.5.8 Self-tuning start

Start condition:

w For process evaluation, a stable condition is required. Therefore, the

controller waits until the process has reached a stable condition after
self-tuning start.
The rest condition is considered being reached, when the process value
oscillation is smaller than

± 0,5% of (rnG.H - rnG.L).

w For self-tuning start after start-up, a 10% difference from (SP.LO ... SP.Hi)

is required.

g

Self-tuning start can be blocked via BlueControl

®

(engineering tool) (

P.Loc).

Strt = 0

Only manual start by pressing keys Ù and È
simultaneously or via interface is possible.

Strt = 1

Manual start by press keys Ù and È simultaneously
via interface and automatic start after power-on and detection
of process oscillations.

3.5.9 Self-tuning cancellation

By the operator:
Self-tuning can always be cancelled by the operator. For this, press Ù and È
key simultaneously.With controller switch-over to manual mode after self-tuning
start, self-tuning is cancelled. When self-tuning is cancelled, the controller will
continue operating using the old parameter values.

By the controller:
If the Err LED starts blinking whilst self-tuning is running, successful self-tuning
is prevented due to the control conditions. In this case, self-tuning was cancelled
by the controller. The controller continues operating with the old parameters in
automatic mode. In manual mode it continues with the old controller output va-
lue.

Operation

KS 90-1 / KS 92-1

21

Self-tuning

Ada LED status

Signification

blinks

Waiting, until process calms down

lit

Self-tuning is running

off

Self-tuning not activ or ended

1200

1199

°C

°F

SP.2

SP.E

para

func

Ada

Err