5.2 Parameters

Parameter setting level

KS 90-1 / KS 92-1

57

Parameters

Cntr

Name

Value range Description

Default

Pb1

1...9999 1

Proportional band 1 (heating) in phys. dimensions (e.g. °C)

100

Pb2

1...9999 1

Proportional band 2 (cooling) in phys. dimensions (e.g. °C)

100

ti1

0,1...9999

Integral action time 1 (heating) [s]

180

ti2

0,1...9999

Integral action time 2 (cooling) [s]

180

td1

0,1...9999

Derivative action time 1 (heating) [s]

180

td2

0,1...9999

Derivative action time 2 (cooling) [s]

180

t1

0,4...9999

Minimal cycle time 1 (heating) [s]. The minimum impulse

is 1/4 x t1

10

t2

0,4...9999

Minimal cycle time 2 (heating) [s]. The minimum impulse

is 1/4 x t2

10

SH

0...9999

Neutral zone or switching differential for on-off control

[phys. dimensions)

2

Hys.l

0...9999

Switching difference Low signaller [engineering unit]

1

Hys.H

0...9999

Switching difference High signaller [engineering unit]

1

d.SP

-1999...9999

Trigger point seperation for additional contact

D / Y /

Off [phys. dimensions]

100

tP

0,1...9999

Minimum impulse [s]

OFF

tt

3...9999

Motor travel time [s]

60

Y.Lo

-120...120

Lower output limit [%]

0

Y.Hi

-120...120

Upper output limit [%]

100

Y2

-100...100

2. correcting variable

0

Y.0

-100...100

Working point for the correcting variable [%]

0

Ym.H

-100...100

Limitation of the mean value Ym [%]

5

L.Ym

0...9999

Max. deviation xw at the start of mean value calculation

[phys. dimensions]

8

E.H2O

-1999...9999

Min. temperature for water cooling. Below the set

temperature no water cooling happens

0

t.on

0,1...9999

Impulse lenght for water cooling. Fixed for all values of

controller output.The pause time is varied.

1

t.oFF

1...9999

Min. pause time for water cooling. The max. effective

controller output results from

t.on/(t.on+t.off)·100%

10

F.H2O

0,1...9999

Modification of the (non-linear) water cooling

characteristic (see page 46)

1

oFFS

-120...120

Zero offset

0

tEmp

0...9999

Sensor temperature (in engineering units e.g. °C)

With oxygen measurement (O

2

) (see page 66)

750

1Valid for ConF/ othr/ dP = 0. With dP = 1 / 2 / 3 also 0,1 / 0,01 /
0,001 is possible.