Configuration 33, Inp.2, Inp.3 – West Control Solutions KS 92-1 User Manual

Page 33

Advertising
background image

Configuration level

KS 90-1 / KS 92-1

33

Configuration parameters

InP.2

Name

Value range Description

Default

I.Fnc

Function selection of INP2

1

0

no function (subsequent input data are skipped)

1

heating current input

2

external set-point (

SP.E)

3

Yp input

4

Second process value X2

5

External positioning value Y.E (switch-over r

LOGI / Y.E)

6

no controller input (e.g. transmitter input instead)

7

Process value x1

S.tYP

Sensor type selection

30

30

0...20mA / 4...20mA 1

31

0...50mA AC 1

50

Potentiometer ( 0...160 Ohm) 1

51

Potentiometer ( 0...450 Ohm) 1

52

Potentiometer ( 0...1600 Ohm) 1

53

Potentiometer ( 0...4500 Ohm) 1

Corr

Measured value correction / scaling

0

0

Without scaling

1

Offset correction (at

CAL level)

(offset entry is at controller

CALlevel)

2

2-point correction (at

CALlevel)

(calibration is at controller

CALlevel)

3

Scaling (at

PArA level)

In.F

-1999...999

9

Alternative value for error at INP2
If a value is adjusted, this value is used for display and

calculation in case of error (e.g. FAIL).

a Before activating a substitute value, the effect in the

control loop should be considered!

OFF

fAI2

Forcing INP2 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

1 with current and voltage input signals, scaling is required (see chapter 5.3)

InP.3

Name

Value range Description

Default

I.Fnc

Function selection of INP3

1

0

no function (subsequent input data are skipped)

1

heating current input

2

External set-point

SP.E (switch-over -> LOGI/ SP.E)

3

Yp input

4

Second process value X2

5

External positioning value Y.E (switch-over r

LOGI / Y.E)

6

no controller input (e.g. transmitter input instead)

7

Process value x1