2 configuration parameters 30, Configuration parameters 30 - 43, Cntr – West Control Solutions KS 92-1 User Manual
Page 30: 2 configuration parameters

4.2 Configuration parameters
Configuration level
Configuration parameters
30
KS 90-1 / KS 92-1
Cntr
Name
Value range Description
Default
SP.Fn
Basic configuration of setpoint processing
0
0
set-point controller can be switched over to external set-point
(->
LOGI/ SP.E)
8
standard controller with external offset (
SP.E)
C.tYP
Calculation of the process value
0
0
standard controller (process value = x1)
1
ratio controller (x1/x2)
2
difference (x1 - x2)
3
Maximum value of x1and x2. It is controlled with the bigger
value. At sensor failure it is controlled with the remaining
actual value.
4
Minimum value of x1and x2. It is controlled with the smaller
value. At sensor failure it is controlled with the remaining
actual value.
5
Mean value (x1, x2). With sensor error, controlling is
continued with the remaining process value.
6
Switchover between x1 and x2 (->
LOGI/ I.ChG)
7
O
2
function with constant sensor temperature
8
O
2
function with measured sensor temperature
C.Fnc
Control behaviour (algorithm)
1
0
on/off controller or signaller with one output
1
PID controller (2-point and continuous)
2
D / Y / Off, or 2-point controller with partial/full load
switch-over
3
2 x PID (3-point and continuous)
4
3-point stepping controller
5
3-point stepping controller with position feedback Yp
6
continuous controller with integrated positioner
C.dif
Output action of the PID controller derivative action
0
0
Derivative action acts only on the measured value.
1
Derivative action only acts on the control deviation
(set-point is also differentiated)
mAn
Manual operation permitted
0
0
no
1
yes (r
LOGI / mAn)
C.Act
Method of controller operation
0
0
inverse, e.g. heating
The correcting variable increases with decreasing process
value and decreases with increasing process value.
1
direct, e.g. cooling
The correcting variable increases with increasing process
value and decreases with decreasing process value.