5 configuration examples 48, 1 on-off controller / signaller (inverse) 48, Signaller 48 – West Control Solutions KS 92-1 User Manual
Page 48
Advertising

4.5 Configuration examples
4.5.1 On-Off controller / Signaller (inverse)
ConF / Cntr:
SP.Fn
=
0
set-point controller
C.Fnc
=
0
signaller with one output
C.Act
=
0
inverse action
(e.g. heating applications)
ConF / Out.1:
O.Act
=
0
action
Out.1 direct
Y.1
=
1
control output Y1 active
PArA / Cntr:
Hys.l
= 0...9999
switching difference below
SP
PArA / Cntr:
Hys.H
= 0...9999
switching difference above
SP
PArA / SEtP:
SP.LO
= -1999...9999
set-point limit low for Weff
SP.Hi
= -1999...9999
set-point limit high for Weff
g
For direct signaller action, the controller action must be changed
(
ConF / Cntr / C.Act = 1 )
Configuration level
Configuration examples
48
KS 90-1 / KS 92-1
InH.1
InL.1
SP.LO
SP
SP.Hi
100%
0%
SH
Out.1Â
InP.1Ê
setpoint
output
process value
SH
Advertising