4.5 Configuration examples

4.5.1 On-Off controller / Signaller (inverse)

ConF / Cntr:

SP.Fn

=

0

set-point controller

C.Fnc

=

0

signaller with one output

C.Act

=

0

inverse action
(e.g. heating applications)

ConF / Out.1:

O.Act

=

0

action

Out.1 direct

Y.1

=

1

control output Y1 active

PArA / Cntr:

Hys.l

= 0...9999

switching difference below

SP

PArA / Cntr:

Hys.H

= 0...9999

switching difference above

SP

PArA / SEtP:

SP.LO

= -1999...9999

set-point limit low for Weff

SP.Hi

= -1999...9999

set-point limit high for Weff

g

For direct signaller action, the controller action must be changed
(

ConF / Cntr / C.Act = 1 )

Configuration level

Configuration examples

48

KS 90-1 / KS 92-1

InH.1

InL.1

SP.LO

SP

SP.Hi

100%

0%

SH

Out.1Â

InP.1Ê

setpoint

output

process value

SH