4.4.3 Switching attitude non-linear (

CyCl= 2 )

With this method, the cooling power is nor-
mally much higher than the heating power,
i.e. the effect on the behaviour during tran-
sition from heating to cooling may be nega-
tive. The cooling curve ensures that the
control intervention with 0 to -70% correc-
ting variable is very weak. Moreover, the
correcting variable increases very quickly to max. possible cooling. Parameter

F.H2O can

be used for changing the characteristic curve. The standard method (see section 4.4.1) is
also used for heating. Cooling is also enabled dependent of process temperature .

Parameters to be adjusted:

F.H2O: adaptation of (non-linear) characteristic

(

PArA / Cntr)

Water cooling

t.on:

Pulse duration water cooling

t.off: min. pause water cooling

E.H2O: min. temperature for water cooling

Configuration level

Switching behaviuor

46

KS 90-1 / KS 92-1

-95%

-67%

-80%

-100%

-92%

-90%

-87%

-82%

t.off

t.on

0

10

20

30

40

50

60

70

-100

-95

-90

-85

-80

-75

-70

-65

-60

-55

-50

-45

-40

-35

-30

-25

-20

-15

-10

-5

Controller output [%]

Water cooling non-linear,

=1

F.H2O

Water cooling non-linear,

=2

F.H2O

Water cooling non-linear,

=0,5

F.H2O

Water cooling linear

Parameter:
t.on = 0.4 sec
t.off = 0.2 sec

Effective

c

ontroller

output