Configuration level

KS 90-1 / KS 92-1

37

Configuration parameters

Out.3

and

Out4

Name

Value range

Description

Default

O.tYP

Signal type selection OUT3

0

0

relay / logic (only visible with current/logic voltage)

1

0 ... 20 mA continuous (only visible with current/logic/voltage)

2

4 ... 20 mA continuous (only visible with current/logic/voltage)

3

0...10 V continuous (only visible with current/logic/voltage)

4

2...10 V continuous (only visible with current/logic/voltage)

5

transmitter supply (only visible without OPTION)

O.Act

MethodofoperationofoutputOUT3(onlyvisiblewhenO.TYP=0)

1

0

direct / normally open

1

inverse / normally closed

Out.0

-1999...9999

Scaling of the analog output for 0% (0/4mA or 0/2V, only

visible when O.TYP=1..5)

0

Out.1

-1999...9999

Scaling of the analog output for 100% (20mA or 10V, only

visible when O.TYP=1..5)

100

O.Src

Signal source of the analog output OUT3 (only visible

when O.TYP=1..5)

1

0

not used

1

controller output y1 (continuous)

2

controller output y2 (continuous)

3

process value

4

effective set-point Weff

5

control deviation xw (process value - set-point)

6

measured value position feedback Yp

7

measured value INP1

8

measured value INP2

9

measured value INP3

O.FAI

Failbehaviour, behaviour of the analog output, if the signal

source (

O.Src) is disturbed.

0

0

upscale

1

downscale

Y.1
Y.2

Controller output Y1/Y2 (only visible when O.TYP=0)

0

0

not active

1

active

Lim.1
Lim.2
Lim.3

Limit 1/2/3 signal (only visible when O.TYP=0)

1

0

not active

1

active

dAc.A

Valve monitoring (DAC) (only visible when O.TYP=0)

0

0

not active

1

active

LP.AL

Interruption alarm signal (LOOP) (only visible when

O.TYP=0) (Loop-Alarm)

0

0

not active

1

active