West Control Solutions KS 92-1 User Manual
Page 32

Configuration level
Configuration parameters
32
KS 90-1 / KS 92-1
Name
Value range Description
Default
4
thermocouple type S (0...1760°C), PtRh-Pt10%
5
thermocouple type R (0...1760°C), PtRh-Pt13%
6
thermocouple type T (-200...400°C), Cu-CuNi
7
thermocouple type C (0...2315°C), W5%Re-W26%Re
8
thermocouple type D (0...2315°C), W3%Re-W25%Re
9
thermocouple type E (-100...1000°C), NiCr-CuNi
10
thermocouple type B (0/100...1820°C), PtRh-Pt6%
18
special thermocouple
20
Pt100 (-200.0 ... 100,0 °C)
( -200,0 ... 150,0°C with reduced lead resistance: measuring
resistance + lead resistance ß160 [ )
21
Pt100 (-200.0 ... 850,0 °C)
22
Pt1000 (-200.0 ... 850.0 °C)
23
special 0...4500 Ohm (preset to KTY11-6)
24
special 0...450 Ohm
30
0...20mA / 4...20mA 1
40
0...10V / 2...10V 1
41
special -2,5...115 mV 1
42
special -25...1150 mV 1
50
potentiometer 0...160 Ohm 1
51
potentiometer 0...450 Ohm 1
52
potentiometer 0...1600 Ohm 1
53
potentiometer 0...4500 Ohm 1
S.Lin
Linearization(onlyat
S.tYP=23(KTY11-6), 24 (0...450W),30
(0..20mA),40(0..10V),41(0...100mV)and 42(special-25...1150mV))
0
0
none
1
Linearization to specification. Creation of linearization table
with BlueControl (engineering tool) possible. The
characteristic for KTY 11-6 temperature sensors is preset.
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at
CAL level)
(controller offset adjustment is at
CALlevel)
2
2-point correction (at
CAL level)
(calibration is at the controller
CALlevel)
3
Scaling (at
PArA level)
4
Autom. calibration (only with positionfeedback Yp)
In.f
-1999...999
9
Alternative value for error at INP1
If a value is adjusted, this value is used for display and
calculation in case of error (e.g. FAIL).
a Before activating a substitute value, the effect in the
control loop should be considered!
OFF
fAI1
Forcing INP1 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
1 with current and voltage input signals, scaling is required (see chapter 5.3)