West Control Solutions KS 92-1 User Manual

Page 34

Advertising
background image

Configuration level

Configuration parameters

34

KS 90-1 / KS 92-1

Name

Value range Description

Default

S.Lin

Linearization (onlyat

S.tYP=30(0..20mA)and40(0..10V)adjustable)

0

0

none

1

Linearization to specification. Creation of linearization table

with BlueControl (engineering tool) possible. The

characteristic for KTY 11-6 temperature sensors is preset.

S.tYP

Sensor type selection

30

0

thermocouple type L (-100...900°C) , Fe-CuNi DIN

1

thermocouple type J (-100...1200°C) , Fe-CuNi

2

thermocouple type K (-100...1350°C), NiCr-Ni

3

thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

thermocouple type S (0...1760°C), PtRh-Pt10%

5

thermocouple type R (0...1760°C), PtRh-Pt13%

6

thermocouple type T (-200...400°C), Cu-CuNi

7

thermocouple type C (0...2315°C), W5%Re-W26%Re

8

thermocouple type D (0...2315°C), W3%Re-W25%Re

9

thermocouple type E (-100...1000°C), NiCr-CuNi

10

thermocouple type B (0/100...1820°C), PtRh-Pt6%

18

special thermocouple

20

Pt100 (-200.0 ... 100,0 °C)
( -200,0 ... 150,0°C with reduced lead resistance: measuring

resistance + lead resistance ß160 [ )

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0 ... 850.0 °C)

23

special 0...4500 Ohm (preset to KTY11-6)

24

special 0...450 Ohm

30

0...20mA / 4...20mA 1

41

special -2,5...115 mV 1

42

special -25...115 0mV 1

50

potentiometer 0...160 Ohm 1

51

potentiometer 0...450 Ohm 1

52

potentiometer 0...1600 Ohm 1

53

potentiometer 0...4500 Ohm 1

Corr

Measured value correction / scaling

0

0

Without scaling

1

Offset correction (at

CAL level)

(offset entry is at controller

CALlevel)

2

2-point correction (at

CAL level)

(calibration is at controller

CALlevel)

3

Scaling (at

PArA level)

4

Automatic calibration (DAC)

In.F

-1999...999

9

Alternative value for error at INP3
If a value is adjusted, this value is used for display and

calculation in case of error (e.g. FAIL).

a Before activating a substitute value, the effect in the

control loop should be considered!

OFF

fAI3

Forcing INP3 (only visible with BlueControl!)

0

0

No forcing

1

Forcing via serial interface

1 with current and voltage input signals, scaling is required (see chapter 5.3)

Advertising
This manual is related to the following products: