West Control Solutions KS 92-1 User Manual
Page 34

Configuration level
Configuration parameters
34
KS 90-1 / KS 92-1
Name
Value range Description
Default
S.Lin
Linearization (onlyat
S.tYP=30(0..20mA)and40(0..10V)adjustable)
0
0
none
1
Linearization to specification. Creation of linearization table
with BlueControl (engineering tool) possible. The
characteristic for KTY 11-6 temperature sensors is preset.
S.tYP
Sensor type selection
30
0
thermocouple type L (-100...900°C) , Fe-CuNi DIN
1
thermocouple type J (-100...1200°C) , Fe-CuNi
2
thermocouple type K (-100...1350°C), NiCr-Ni
3
thermocouple type N (-100...1300°C), Nicrosil-Nisil
4
thermocouple type S (0...1760°C), PtRh-Pt10%
5
thermocouple type R (0...1760°C), PtRh-Pt13%
6
thermocouple type T (-200...400°C), Cu-CuNi
7
thermocouple type C (0...2315°C), W5%Re-W26%Re
8
thermocouple type D (0...2315°C), W3%Re-W25%Re
9
thermocouple type E (-100...1000°C), NiCr-CuNi
10
thermocouple type B (0/100...1820°C), PtRh-Pt6%
18
special thermocouple
20
Pt100 (-200.0 ... 100,0 °C)
( -200,0 ... 150,0°C with reduced lead resistance: measuring
resistance + lead resistance ß160 [ )
21
Pt100 (-200.0 ... 850,0 °C)
22
Pt1000 (-200.0 ... 850.0 °C)
23
special 0...4500 Ohm (preset to KTY11-6)
24
special 0...450 Ohm
30
0...20mA / 4...20mA 1
41
special -2,5...115 mV 1
42
special -25...115 0mV 1
50
potentiometer 0...160 Ohm 1
51
potentiometer 0...450 Ohm 1
52
potentiometer 0...1600 Ohm 1
53
potentiometer 0...4500 Ohm 1
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at
CAL level)
(offset entry is at controller
CALlevel)
2
2-point correction (at
CAL level)
(calibration is at controller
CALlevel)
3
Scaling (at
PArA level)
4
Automatic calibration (DAC)
In.F
-1999...999
9
Alternative value for error at INP3
If a value is adjusted, this value is used for display and
calculation in case of error (e.g. FAIL).
a Before activating a substitute value, the effect in the
control loop should be considered!
OFF
fAI3
Forcing INP3 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
1 with current and voltage input signals, scaling is required (see chapter 5.3)