Optimization-at-the-set-point procedure:
The controller uses its instantaneous parameters for control to the set-point. In li-
ned out condition, the controller makes a pulse attempt. This pulse reduces the
correcting variable by max. 20% 1, to generate a slight process value unders-
hoot. The changing process is analyzed and the parameters thus calculated are re-
corded in the controller. The optimized parameters are used for line-out to
theset-point.

With a 3-point controller, optimization for the “heating“ or “cooling” parameters
occurs dependent of the instantaneous condition.
These two optimizations must be started separately.

1 If the correcting variable is too low for reduction in lined out condition it is
increased by max. 20%.

Operation

KS 90-1 / KS 92-1

19

Self-tuning

set-point

process value

correcting
variable

Optimization at the set-point