1.5 Certifications

1.5.1

European EMC Directive

If the SK 1x5E is installed according to the recommendations in this manual,
it meets all EMC directive requirements, as per the EMC product standard
for semiconductor motor control devices EN 60947-4. (see also Section 7.3,
Electromagnetic Compatibility [EMC].)

1.5.2

UL and cUL approval

(in preparation)

At present the approvals are in the process of preparation.

All SK 1x5E motor starters include motor overload protection. Further technical details can be found in
Section 7.2.

NOTE

"Integral solid state short circuit protection does not provide branch circuit protection. Branch
circuit protection must be provided in accordance with the National Electric Code and any
additional local codes."

NOTE

“The device has to be mounted according to the manufacturer instructions.”


"Use 80°C Copper Conductors Only"
(only refers to connection cables (mains and motor cables but not control cables)

"These products are intended for use in a pollution degree 2 environment"

cUL Approval - File No. E171342

“Suitable For Use On A Circuit Capable Of Delivering Not More Than 100000 rms
Symmetrical Amperes, 500 Volts maximum and when protected by RK5 class or faster
fuses as indicated in chapter 7.2.”

“Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms Symmetrical Amperes, 500 Volts
maximum and when protected by Circuit Breaker (inverse time trip type) in accordance with UL 489”, current and
voltage ratings according to instruction manual.

„The torque value for the field wiring terminals for mains circuit terminals, motor terminals, break terminals and breaking
resistor terminals must be 11 … 15 lb-in (1.2 … 1.5Nm). The torque value for the field wiring terminals for control circuit
terminals must be 4.4 … 5.3 lb-in (0.5 … 0.6Nm).”