2 details of the sk 1x5e control connections – NORD Drivesystems BU0135 User Manual

Page 30

Advertising
background image

SK 105E…175E Motor Starter Manual

30

Pre-series version

BU 0135 GB-2713

2.6.2

Details of the SK 1x5E control connections

Control voltage 24V external! Terminal 44. If the motor starter is not equipped with an optional mains unit it
must be supplied with an external 24V voltage.

For devices with which the AS interface is used, the supply voltage can be taken from the AS interface cable
if the appropriate jumpers are set ("only yellow cable"). Otherwise the device can also have a separate
supply ("black and yellow cable"). In this case, the jumpers must not be set.

Terminal/

Name

Function

{Factory setting}

Data

Description /
wiring suggestion

Parameter


SK 105E…SK175E

44

VI 24V

24V supply

Input

24VDC ±25%

50mA (Starter without
accessories) ... 400mA
according to load on the
inputs and outputs or
equipment with options

Connection of the supply voltage
for the control unit and supply to
outputs DOUT1+2 as well as any
connected initiators

-

40 GND / 0V

Reference potential
for digital signals

-

21

DIN1

Digital input 1

{ON right}

Digital input as per
EN 61131-2, Type 1

Low: 0-5V

(~ 9.5k

Ω)

High: 15-30V

(~ 2.5-3.5k

Ω)

Input capacitance: 10nF

Scanning time: 1ms

Reaction time:

≥ 4ms

For control of the device from an
external control unit or switch.

P420 [01]

22

DIN2

Digital input 2

{ON left}

P420 [02]

1

DOUT1

Output 1

{Error}

Digital output

18-30V, each to VI 24V

max. 200mA

Devices with AS-I
(SK 145E or higher):
Total current 165 mA

max. 100k

Wload

For evaluation in a control system.

P434 [01]

3

DOUT2

Output 1

{Starter running}

P434 [02]

38

TF+

PTC resistor input

-

For monitoring the motor
temperature by PTC.

-

39

TF-

PTC resistor input

79

MB+

Brake control

Voltage:
Mains

brake

230V

105V=

400V~

180V=

460/480V~

205V=

Current: max. 0.5A

The motor starter generates an
output voltage on Terminals
MB+/MB- for control of an
electromagnetic brake. This
depends on the supply voltage to
the SK 1x5E.

It is essential to take the correct
brake coil voltage into account in
the selection.

P107,
P114,

80

MB-

Brake control

Advertising