SK 105E…175E Motor Starter Manual

62

Pre-series version

BU 0135 GB-2713

5.1.1

Operating displays

Parameter

{ Factory setting }

Setting value / Description / Note

READ

RAM

READ /

FLASH

FLASH

P000

Operating para. disp.

(Operating parameter display)

x

0.01 ... 9999

In the SimpleBox (SK CSX-3H) display, the parameter value online selected in P100 is
displayed.

P001

Select of disp.value

(Selection of display value)

x

0 ... 11

{ 0 }

0 = Actual frequency [Hz], is the actual output frequency being supplied by the starter.

1 = Mains frequency [Hz], is the frequency of the mains voltage.

2 = Current [A], the actual output current measured by the starter.

3 = Effective current [A], is the effective current which is supplied by the motor starter.

4 = Reactive current [A], is the reactive current which is supplied by the motor starter.

5 = Mains voltage [V~ ], is the voltage which is applied to the input of the starter.

6 = cos phi, the currently calculated value of the power factor.

7 = Apparent power [kVA], the actual apparent power calculated by the starter.

8 = Effective power [kW], the actual effective power calculated by the starter.

9 = Mains phase sequence, 0 = right hand field of rotation, 1 = left hand field of rotation.

10 = Degree of phase control [%].

11 = Actual current amplification

P003

Supervisor code

(Supervisor code)

x

0 ... 9999

{ 1 }

0 = The Supervisor parameters are not visible. Otherwise, all parameters are visible.

1 = All parameters are visible

10

.

2 = ... 9999, (except 65) only parameters P001 and P003 are visible.

10

In the following, supervisor parameters are designated with "S"; normal parameters are designated with "x"