7 Technical data

BU 0135 GB-2713

Pre-series version

81

7.2 Motor starter electrical data

The following table lists the electrical data for SK1x5E series motor starters.

Size 1

Device type:

SK 1x5E…

-301-340-A

-751-340-A

Nominal motor power

(4-pole standard motor)

400V

3.0 kW

7.5 kW

480V

4 hp

10 hp

Input

Mains voltage

3~ 200V…500V

3 AC 200V-10%...500V+10%, 47 ... 63 Hz

Typical input
current at 400V

3~ rms

7.5 A

16.0 A

3~ FLA

7.5 A

16.0 A

Rec. mains fuse

1 AC

slow-acting [A]

16 A

25 A

Permissible
mains fuses (UL)

RK5 or faster

fuses,

min 230V/400V

15.0 A

25.0 A

Bussmann

FRS-R-15

FRS-R-25

Circuit breaker*

min. 230V/400V

15.0 A

25.0 A

O

ut

put

Output voltage

3~ 200V…500V

3 AC Mains voltage

Nominal output
current at 400V

rms

7.5 A

16.0 A

Maximum continuous power / max. continuous current:

S1-50°C

3.00kW / 7.5A

7.5kW / 16.0A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

50°C

60°C

60°C

50°C

60°C

60°C

Wall-mounted (unventilated)

Maximum continuous power / max. continuous current:

S1-50°C

S1-60°C

3.00kW / 7.5A

2.20kW / 5.5A

7.50kW / 16.0A

5.50kW / 12.5A

Max. permissible ambient temp. with nominal output current

S1

S3

70%ED 10min

S6

70%ED 10min (100% / 20%Mn)

50°C

60°C

60°C

50°C

60°C

60°C

* Circuit Breaker (inverse time trip type) as per UL489