3 control connections for sk 1x5e communication – NORD Drivesystems BU0135 User Manual

Page 31

Advertising
background image

2 Assembly and installation

BU 0135 GB-2713

Pre-series version

31


Additionally for SK 145E ... SK 175E

43

24V

24V supply

Output

24VDC ±25%

165mA

Connection of the supply voltage
for the control unit and supply to
outputs DOUT1+2 as well as any
connected initiators

-

40 GND / 0V

Reference potential
for digital signals

-

C1

DIN3

Digital input 3

{ON right}

Digital input as per
EN 61131-2, Type 1

Low: 0-5V

(~ 9.5k

Ω)

High: 15-30V

(~ 2.5-3.5k

Ω)

Input capacitance: 10nF

Scanning time: 1ms

Reaction time:

≥ 4ms

Digital input for the evaluation of a
connected initiator. This input is
transferred to the control unit
directly via the AS interface or the
PROFIBUS. It is not evaluated by
the starter.

-

C2

DIN4

Digital input 4

{ON left}

-

84

ASI+

Actor Sensor
Interface

4

26.5 – 31.6V,
max. 240mA

For control of the SK 1x5E via the
simple field bus level.

By means of jumpers it can be
selected whether only the "yellow
cable" is used, or "yellow" and
"black", i.e. supply with additional
auxiliary power.

-

85

ASI-

82

PBR-B

PROFIBUS DP

5

For control of the SK 1x5E via
PROFIBUS DP.

-

83

PBR-A

2.6.3

Control connections for SK 1x5E communication

Terminal/
Designation

Function
{Factory setting}

Data

Description / wiring suggestion

Parameter


all SK 1x5E, connector block RJ12, RS232

3

GND

Reference potential
for Bus signals

0V digital

R

S

485_

A

R

S

485_

B

GN

D

TX

D

RX

D

+

5V

+

24V

n

.c

.

n

.c

.

RJ12: Pin No. 1 … 6
1: n.c.
2: n.c.
3: GND
4: RS232_TxD
5: RS232_RxD
6: +24V

4

232 TXD

Data cable RS232

Baud rate 38400Baud
Address 0
USS protocol

5

232 RXD

6

+24V

24V supply voltage
from the FI

24V

± 20%

4

SK145E…SK175E with integrated AS interface

5

SK145E…SK175E with integrated PROFIBUS