3 electro-mechanical brake – NORD Drivesystems BU0135 User Manual

Page 27

Advertising
background image

2 Assembly and installation

BU 0135 GB-2713

Pre-series version

27

2.5.3

Electro-mechanical brake

Connection of an electromagnetic brake is possible for all SK 1x5E devices. To control the brake, an output
voltage is generated to terminals 79 / 80 (MB+ / MB-) by the motor starter to terminals 79 / 80 (MB+ / MB-)
(also refer to Sections 2.6.1 to 2.6.2). This depends on the supply voltage. The assignment is as follows:

Mains voltage / Alternating current (AC)

Brake coil voltage (DC)

230 V ~

105 V =

400 V ~

180 V =

460 V ~ / 480 V ~

205 V =

The allocation of the correct brake or brake coil voltage must be taken into account in the design with refer-
ence to the mains voltage of the motor starter.

NOTE

For the connection of a mechanical brake to the terminals of the motor starter, parameters
P107 / P114 (brake application time / release time ) must be adjusted. In order to prevent
damage to the brake control, a value

≠ 0 must be set in parameter (P107).

The following settings for (P107/P114) are recommended for NORD brakes:
BRE5, BRE10, BRE40 :

0.02s,

BRE20, BRE60, BRE100, BRE150:

0.03s,

BRE250:

0.04s,

Connection terminals:

Screw terminals, 0.6 x 3.5 mm slot-head screwdriver

Connection cross-section: 0.2 ... 2.5mm

2

, AWG 24-14, rigid or flexible, without wire end sleeves

Brake connection terminal 79/80

Advertising