3.1 Diagnostic LEDs on the motor starter

The motor starter generates operating status messages. These messages (warnings, errors, switching sta-
tuses, measurement data) can be displayed with parameterisation tools (e.g. ParameterBox - see Section
3.2) (Parameter group P7xx).

To a limited extent, the messages are also indicated via the diagnostic and status LEDs.

Diagnostic LEDs

LED

Name

Colour

Description

Signal status

Meaning

DS

dual

red/green

Device status

off

Starter not ready for operation,

Þ

no control voltage

green on

Starter is switched on (running)

green
flashing

0.5 Hz

Starter is ready for switch-on

4 Hz

Starter is in switch-on block

red/green

4 Hz

Warning

Alternating

0.5 Hz

Starter is not ready for switch-on

Þ

24V supply available, but no

mains voltage

red
flashing

Error, flashing frequency → Error number

AS-I

dual

AS-i status

off

No voltage to the AS-I module (PWR)

red/green

green

Normal operation

red

No exchange of data

Þ

Slave Address = 0 / Slave not in LPS /

Slave with incorrect IO/ID /

Master in

STOP mode / Reset active

alternately
flashing
red / yellow

2 Hz

no exchange of data

à Slave address = 0

alternately
flashing
red / green

2 Hz

Peripheral error

red
flashing

2 Hz

EMC / Hardware error

PBR

green

Status PBR

off

No cyclic process data communication

active

green

Normal operation, cyclic process data communi-

cation in operation

NOTE

If there is active RS232 communication to a PC (NORD CON) or connected
control boxes, the device status cannot be displayed. In this case the LED indi-
cates that there is communication and in general is therefore always "green".
In this case the red LED is switched off. If the current potentiometer is adjusted,
the green LED may also flicker due to the operating principle.