5 Parameterisation

BU 0135 GB-2713

Pre-series version

67

5.1.4

Control terminals

Parameter

{ Factory setting }

Setting value / Description / Note

READ

RAM

READ /

FLASH

FLASH

P400

[-01]

[-04]

Fnct. Potentiometer

(Potentiometer function)

x

0 ... 6

{ [-01] = 1 }
Rated current of
motor

{ [-02] = 2, 5

11

}

Locking time
Acceleration time

{ [-03] = 3 }
Starting torque

{ [-04] = 4, 6

12

}

Ramp time
Deceleration time

Here the set functions for up to four potentiometers can be viewed. It is not possible to change
the setting.

0 = No function, the potentiometer is not used

1 = Rated motor current, value for P203 as long as P130=0

2 = Locking time, value for P570 as long as P130=0

3 = Starting torque, value for P210 as long as P130=0

4 = Ramp times, value for P102 and P103 as long as P130=0

5 = Acceleration time, value for P102 as long as P130=0

6 = deceleration time, value for P103 as long as P130=0

P420

[-01]

[-07]

Digital inputs

(digital input functions)

x

0 ... 9

{ [-01] = 1 } Digital
input 1

{ [-02] = 2 } Digital
input 2

{ [-03] = 8 }

13

Thermistor

{ [-04] = 3 }
Bus In Bit 0

{ [-05] = 4 }
Bus In Bit 1

{ [-06] = 7 }
Bus In Bit 2

{ [-07] = 9 }
Bus In Bit 3

Here the set functions for up to seven digital inputs can be viewed. It is possible to change the
setting if parameter P130=1 is set. Otherwise the value can only be views and is fixed.

0 = No function

1 = Enable right (only possible for digital input 1 and 2)

2 = Enable left (only possible for digital input 1 and 2)

3 = Enable right via bus (only possible for digital inputs 4 to 7)

4 = Enable left via bus (only possible for digital inputs 4 to 7)

5 = Block voltage

6 = Quick stop

7 = Error acknowledgement

8 = PTC resistor input

9 = Release the brake

P427

Emerg. stop

Error

(Emergency stop on error)

x

0 ... 1

{ 0}

In case of errors E2.0, E3.0, E5.1 and E6.1 there is the option that the drive is not switched off
immediately if the error occurs, but rather with devices with a soft start function, these are run
down the ramp as normal before switch-off.

0 = Disabled: Automatic quick stop following error is deactivated

1 = Activated: Automatic quick stop following error is activated

11

Acceleration time for type SK 115E and SK 155E devices (5) – Locking time for all other devices (2)

12

Deceleration time for type SK 115E and SK 155E devices (6) – Ramp time for all other devices (4)

13

The thermistor input cannot be re-programmed to another function.