NORD Drivesystems BU0135 User Manual

Page 71

Advertising
background image

5 Parameterisation

BU 0135 GB-2713

Pre-series version

71

Parameter

{ Factory setting }

Setting value / Description / Note

READ

RAM

READ /

FLASH

FLASH

P580

Error on overtemp.

(Error on overtemperature)

x

0 ... 1

{ AN / DIP2/4}

0 = Disabled: In case of overtemperature, only a warning is active, but no error message

and the corresponding switch-off on error.

1 = Activated: In case of overtemperature, the device switches off with error message E002.

NOTE: As long as P130=0 is set, P580 is determined by DIP switch 2 for SK 105E, SK 115E,
SK 145E and SK 155E devices and by DIP switch 4 for SK 125E and SK 165E devices. In this
case, the parameter can only be read and not changed and corresponds to the value which is
set by the DIP switch.

P581

Phase sequence detection

(Phase sequence detection)

x

0 ... 1

{ AUS / DIP2}

For devices with a reversing function there is the option of analysing the mains phase sequence
and therefore adapting the enabling direction to the field rotation. If there is a "left field of
rotation" on the mains side, in case of "Enable right" the switches would be activated, which
would otherwise mean "Direction of rotation left", so that the required rotation field is produced
in the motor. If the phase sequence detection is disabled, the direction of rotation of the mains
always determines the direction of rotation of the motor.

0 = Disabled: No phase sequence detection.

1 = Activated: Phase sequence detection is activated.

NOTE: As long as P130=0 is set, for devices with reversing function (125E, 135E, 165E and
175E) P581 is determined by DIP switch 2. In this case, the parameter can only be read and not
changed and corresponds to the value which is set by the DIP switch.

P582

Man. release brake

(Release brake manually)

x

0 ... 1

{ AUS / DIP3}

In order to be able to release the electromechanical motor brake (even if the motor is not to be
enabled) there is the option of implementing this via parameter 582 or DIP switch 3. In general,
this is only necessary if a drive is to be moved manually, e.g. for maintenance work.

0 = Disabled: The brake is only released when the motor is enabled.

1 = Activated: The brake is released even if the motor is not enabled.

NOTE: As long as P130=0 is set, for devices without a soft start function (105E, 125E, 145E
and 165E) P582 is determined by DIP switch 3. In this case, the parameter can only be read
and not changed and corresponds to the value which is set by the DIP switch.

Advertising