Digital 2 point output – without diagnostic status – Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 109

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 95

Digital 2 POINT Output –

Without Diagnostic Status

1734-OA2

2 POINT 120V AC Output

1734-OW2

2 POINT AC/DC Relay Output

1734-OX2

2 POINT Relay Output N.O./N.C.
Configuration Data

Data Type

Default

Value

Valid Data Values

Fault Mode - POINT 0, 1

SINT, BIT

0

0=Fault Value

1=Hold Last State

Fault Value - POINT 0, 1

SINT, BIT

0

0=Off

1=On

Program Mode - POINT 0, 1

SINT, BIT

0

0=Program Value

1=Hold Last State

Program Value - POINT 0, 1

SINT, BIT

0

0=Off

1=On

Input Data

Data Type

Default

Value

Valid Data Values

None

Output Data

Data Type

Default

Value

Valid Data Values

Output Data - POINT 0, 1

SINT, BIT

0

0=Off

1=On