Publication 1734-UM011D-EN-P - May 2011

52 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software

4. Enter values for Name, IP Address, Comm Format, Chassis Size,

Electronic Keying, and Revision, noting we used the following values.

Comm Format choices include:

None – the adapter makes a direct connection to each of the

modules referenced by the data.

Rack optimization – digital I/O data is collected into a rack image.

This does not include analog or specialty I/O modules.

Listen only - rack optimization – read or verify data only, but does

not control the modules. When you have multiple controllers, one
controller is used to control and the other controllers are used to
monitor.

5. Choose Rack Optimization as Comm Format, because we are making a

mixed connection that includes both a direct connection and
rack-optimized connection.

6. Click OK.

The Module Properties dialog opens.

Name

POINT_IO_Adapter

IP Address

10.88.70.2

Comm Format

Rack Optimization

Chassis Size

4

Electronic Keying

Compatible Keying

Revision

1.1

The Slot field appears grey because the slot is automatically 0 for the

1734-AENT adapter.

IMPORTANT

The chassis size equals 1 for the adapter plus the number of
POINT I/O modules installed (physically present on the
POINT I/O backplane).