Publication 1734-UM011D-EN-P - May 2011

124 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference

SSI Word Delay Time

To enter Delay values from +32,768…+65,535

µs, use this conversion

formula:

Desired Delay Value (in

µs) - 65536 = Entered Delay Value (in µs).

As an example, for a 40 ms delay time, 40000 - 65536 = -25536

Sensor Resolution

To enter Resolution values from +32,768…+65,535

µs, use this conversion

formula:

Desired Resolution Value - 65536 = Entered Resolution Value.
As an example, for a 40,000 count sensor, 40000 - 65536 = -25536

Sensor Cycle

To enter Cycle values from +32,768…+65,535, use this conversion formula:

Desired Cycle Value - 65536 = Entered Cycle Value.
As an example, for 50,000 sensor cycle rotations, 50000 - 65536 =
-15536

Compare 0,1 Value

To enter Compare values from +2,147,483,647…+4,294,967,295, use this
conversion formula:

Desired Compare Value - 4,294,967,296 = Entered Compare Value.
As an example, for a 3,000,000,000 compare value,
3,000,000,000 - 4,294,967,296 = -1,294,967,296