Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 51

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

Configure the Adapter for Direct Connection in RSLogix 5000 Software 35

4. Enter values for Name and Slot, noting that we used the

following values.

5. Choose Connection.

The RPI is selectable since it is a direct connection.

6. Enter 50 for requested packet interval (RPI) to set how often you

exchange data with the 1734-AENT adapter.

7. Click OK to save the configuration.

The relay output module appears under Ethernet.

Name

POINT_Relay_Output

Slot

1

IMPORTANT

To avoid overloading the 1734-AENT adapter, we
recommend that RPI be no less than 10 ms for rack
connections and 50 ms for direct connections.