Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 61

7. Read and acknowledge the warning dialog.

8. Click OK to continue.

9. Notice the chassis size in the module is modified to 3.

10. Click OK.

At this point, your POINTBus status LED should be solid green. All
the yellow triangles in your I/O configuration tree should be gone.

11. Click OK to close the dialog.