Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 80

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

64 LED Status Indicators

Indication

Probable Cause

Recommended Action

Network Activity
Off

No link established.

Verify network cabling, and correct,

as needed.

Flashing

green/Off

Transmit or receive activity

present.

None

Steady green

Link established.

None

Network Status
Off

Device not initialized. The

module does not have an IP

address.

Apply power to device, verify IP

address, and correct, as needed.

Flashing green No CIP connections present.

Device has an IP address, but no

CIP connections are established.

None

Solid green

CIP connections present. Device

online and has an IP address, and

CIP connections are established.

None

Flashing red

One or more CIP connections has

timed-out.

Check for I/O module failure and

controller operation, and correct, as

needed.

Solid red

Duplicate IP address detected.

Verify IP address setting and correct,

as needed.

Flashing

red/green

The module is performing a

self-test (only occurs during cycle

power test).

None

POINTBus Status
Off

Device not powered – check

module status indicator.

Apply power to device.

Flashing

red/green

LED cycle power test present.

None

Flashing red

Recoverable fault occurred:

• At cycle power the

number of expected

modules does not equal

the number of modules

present

• A module is missing
• Node fault (I/O

connection timeout)

occurred.

• Configure chassis size.

• Check for missing module and

reinstall as needed.

• Check for I/O module failure

and correct as needed.

Solid red

Unrecoverable fault occurred –

the adapter is bus off.

1. Cycle power to device.

2. If condition persists, replace

device.

Flashing green Firmware (NVS) update in

progress.

None

Solid green

Adapter online with connections

established (normal operation,

Run mode).

None