Publication 1734-UM011D-EN-P - May 2011

110 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference

1734-OE2C

2 Channel Analog Current Output
Configuration Data

Data Type

Default

Value

Valid Data Values

Idle Mode Channel 1

SINT

1

0=Hold Last State

1=Go to Low Clamp

2=Go to High Clamp

3=Go to Fault Value

Limit Alarm Latch Channel 1

SINT

0

0=No Latching

1=Alarms Latch

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled

1=Alarms Disabled

Input Data

Data Type

Default

Value

Valid Data Values

Status Byte Channel 0

SINT

0

Bit 0 Fault

Bit 1 Calibration

Bit 2 LowAlarm

Bit 3 HighAlarm

Status Byte Channel 1

SINT

0

Bit 0 Fault

Bit 1 Calibration

Bit 2 LowAlarm

Bit 3 HighAlarm

Output Data

Data Type

Default

Value

Valid Data Values

Data Channel 0

INT

0

-32,768…32,767

Data Channel 1

INT

0

-32,768…32,767