LED Status Indicators 65
System Power
Off
Not active; field power is off or
DC-DC converter problem
present.
1. Verify power is on, and apply
power if needed.
2. Verify backplane power not
exceeded, and correct.
3. Replace 1734-AENT module.
Green
System power is on; DC-DC
converter is active (5V).
None
Field Power
Off
Not active; field power is off.
Apply field power.
Green
Power is on; 24V is present.
None