LED Status Indicators 65

System Power
Off

Not active; field power is off or

DC-DC converter problem

present.

1. Verify power is on, and apply

power if needed.

2. Verify backplane power not

exceeded, and correct.

3. Replace 1734-AENT module.

Green

System power is on; DC-DC

converter is active (5V).

None

Field Power
Off

Not active; field power is off.

Apply field power.

Green

Power is on; 24V is present.

None