Set the network address – Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual
Page 35

Publication 1734-UM011D-EN-P - May 2011
Configure the Adapter for Your EtherNet/IP Network 19
The new configuration is:
A second network with Hosts D and E was added. Gateway G2 connects
Network 2.1 with Network 2.2.
Hosts D and E will use Gateway G2 to communicate with hosts not on
Network 2.2.
Hosts B and C will use Gateway G to communicate with hosts not on
Network 2.1.
When B is communicating with D, G (the configured Gateway for B) will
route the data from B to D through G2.
Set the Network Address
The adapter ships with the thumbwheel switches set to 999 and DHCP
enabled. You can set the network Internet Protocol (IP) address in these ways:
• Use the thumbwheel switches located on the module.
• Use a Dynamic Host Configuration Protocol (DHCP) server, such as
Rockwell Automation BootP/DHCP.
• Retrieve the IP address from nonvolatile memory.
Network 2.1
128.2.64.1
128.1.0.2
128.2.64.3
Network 1
A
B
G2
D
G
Network 2.2
128.1.0.1
128.2.128.1
128.2.128.2
128.2.128.3
128.2.64.2
43248
Network address
thumbwheel
Press either the + or -
buttons to change the
number.