Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual
Page 132

Publication 1734-UM011D-EN-P - May 2011
118 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-VHSC24
1 Channel 15…24V DC Very High-speed Counter
1734-VHSC5
1 Channel 5V DC Very High-speed Counter
Output Data
Data Type
Default
Value
Valid Data Values
PWM Value
INT
0
0…9500
(0.00…95.00%)
Counter Control
Counter Reset
Counter Preset
Value Reset
(Stored / Accumulated Count)
SINT
BIT 0
BIT 1
BIT 2
0
0
0
0
0=Count Unchanged
1=Count Cleared
0=Count Unchanged
1=Count Set to Preset
0=Count Unchanged
1=Count Cleared
Output Control
Output 0 Force
Output 0 Enable
Output 0 Electronic Fuse
Output 0 Diagnostic Speed
Output 1 Force
Output 1 Enable
Output 1 Electronic Fuse
Output 1 Diagnostic Speed
SINT
BIT 0
BIT 1
BIT 2
BIT 3
BIT 4
BIT 5
BIT 6
BIT 7
0
0
0
0
0
0
0
0
0
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0< 8 ms Response
1=50 ms Response
0=Output Off
1=Output Forced On
0=Output Disabled
1=Output Enabled
0=Auto Retry
1=Latch Off
0< 8 ms Response
1=50 ms Response