118 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference

1734-VHSC24

1 Channel 15…24V DC Very High-speed Counter

1734-VHSC5

1 Channel 5V DC Very High-speed Counter
Output Data

Data Type

Default

Value

Valid Data Values

PWM Value

INT

0

0…9500

(0.00…95.00%)

Counter Control

Counter Reset

Counter Preset

Value Reset

(Stored / Accumulated Count)

SINT

BIT 0

BIT 1

BIT 2

0

0

0

0

0=Count Unchanged

1=Count Cleared

0=Count Unchanged

1=Count Set to Preset

0=Count Unchanged

1=Count Cleared

Output Control

Output 0 Force

Output 0 Enable

Output 0 Electronic Fuse

Output 0 Diagnostic Speed

Output 1 Force

Output 1 Enable

Output 1 Electronic Fuse

Output 1 Diagnostic Speed

SINT

BIT 0

BIT 1

BIT 2

BIT 3

BIT 4

BIT 5

BIT 6

BIT 7

0

0

0

0

0

0

0

0

0

0=Output Off

1=Output Forced On

0=Output Disabled

1=Output Enabled

0=Auto Retry

1=Latch Off

0< 8 ms Response

1=50 ms Response

0=Output Off

1=Output Forced On

0=Output Disabled

1=Output Enabled

0=Auto Retry

1=Latch Off

0< 8 ms Response

1=50 ms Response