POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 119

1734-IJ

1 Channel 5V DC Encoder / Counter

1734-IK

1 Channel 15…24V DC Encoder / Counter
Configuration Data

Data Type

Default

Value

Valid Data Values

Counter Config

Config_0

Config_1

Config_2

Config_3

Mode_4

Mode_5

Mode_6

Z Input

SINT

BIT 0

BIT 1

BIT 2

BIT 3

BIT 4

BIT 5

BIT 6

BIT 7

0

0000=0=Counter

0001=1=Encoder X1

0010=2=Encoder X2

0100=4=Encoder X4

0101=5=Period/Rate

0111=7=Rate Measurement

000=Store Count Disable

001=Store/Continue

010=Store/Wait/Resume

011=Store,Reset/Wait/Start

100=Store,Reset/Start

0=Z Input Not Inverted

1=Z Input Is Inverted

Filter

Filter_0

Filter_1

Filter_2

Filter_3

FilterA

FilterB

FilterZ

SINT

BIT 0

BIT 1

BIT 2

BIT 3

BIT 4

BIT 5

BIT 6

120

(0x78H)

0000=No Filter

0001=50 kHz

0010=5 kHz

0100=500 Hz

1000=50 Hz

0=Input A/B/Z Not Filtered

1=Input A/B/Z Is Filtered

Decimal Position

SINT

0

Counter Config 0, 1, 2, 4:

-128…+127 (0…255)

Counter Config 5 & 7:

-4…+2

Time Base

(in 10 ms intervals)

INT

0

Counter Config 7 only:

0…3000 ms (10 ms…3 s)

Gate Interval

(Product of Time Base x Gate Interval

must be

≤ 3000 ms)

SINT

0

Counter Config 7 only:

-128…+127 (0…200)

Scalar

SINT

0

Counter Config 5 only:

-128…+127 (0…255)

0, 1, 2, 4, 8, 16, 32, 64, -128

Rollover

DINT

16,777,215 1…16,777,216

Preset (< Rollover)

DINT

0

0…16,777,215