Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 125

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 111

1734-OE2V

2 Channel Analog Voltage Output
Configuration Data

Data Type

Default

Value

Valid Data Values

Fault Value Channel 0

INT

0

-32,768…32,767

Program Value Channel 0

INT

0

-32,768…32,767

Low Engineering Channel 0

INT

0

-32,768…32,767

High Engineering Channel 0

INT

10,000

-32,768…32,767

Low Limit Channel 0

INT

-32,768

-32,768…32,767

High Limit Channel 0

INT

32,767

-32,768…32,767

Range Type Channel 0

SINT

1

1=0…10V

3=-10…+10V

Fault Mode Channel 0

SINT

1

0=Hold Last State

1=Go to Low Clamp

2=Go to High Clamp

3=Go to Fault Value

Idle Mode Channel 0

SINT

1

0=Hold Last State

1=Go to Low Clamp

2=Go to High Clamp

3=Go to Fault Value

Limit Alarm Latch Channel 0

SINT

0

0=No Latching

1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled

1=Alarms Disabled

Fault Value Channel 1

INT

0

-32,768…32,767

Program Value Channel 1

INT

0

-32,768…32,767

Low Engineering Channel 1

INT

0

-32,768…32,767

High Engineering Channel 1

INT

10,000

-32,768…32,767

Low Limit Channel 1

INT

-32,768

-32,768…32,767

High Limit Channel 1

INT

32,767

-32,768…32,767

Range Type Channel 1

SINT

1

1=0…10V

3=-10…+10V

Fault Mode Channel 1

SINT

1

0=Hold Last State

1=Go to Low Clamp

2=Go to High Clamp

3=Go to Fault Value

Idle Mode Channel 1

SINT

1

0=Hold Last State

1=Go to Low Clamp

2=Go to High Clamp

3=Go to Fault Value