Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual
Page 121

Publication 1734-UM011D-EN-P - May 2011
POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 107
1734-IT2
2 Channel Thermocouple Input, Isol.
Configuration Data
Data Type
Default
Value
Valid Data Values
Temperature Mode Channel 0
SINT
1
0=mV/Custom Scale
1=°C
2=°F
3=°K
4=°R
Cold Junction Enable Channel 0
SINT
1
0=Disabled
1=Enabled
Cold Junction Offset Channel 0
INT
0
0…7,000 (0.00…70.00)
Low Engineering Channel 1
INT
0
-32,768…32,767
High Engineering Channel 1
INT
7,000
-32,768…32,767
Alarm Disable Channel 1
SINT
0
0=Alarms Enabled
1=Alarms Disabled
Limit Alarm Latch Channel 1
SINT
0
0=No Latching
1=Alarms Latch
Notch Filter Channel 1
SINT
1
0=50 Hz
1=60 Hz
2=100 Hz
3=120 Hz
4=200 Hz
5=240 Hz
6=300 Hz
7=400 Hz
8=480 Hz
Sensor Type Channel 1
SINT
5
0=mV
1=B
2=C
3=E
4=J
5=K
6=N
7=R
8=S
9=T
Digital Filter Channel 1
INT
0
0…10,000 ms
Low Alarm Limit Channel 1
INT
-32,768
-32,768…32,767
High Alarm Limit Channel 1
INT
32,767
-32,768…32,767
Low Low Alarm Limit Channel 1
INT
-32,768
-32,768…32,767
High High Alarm Limit Channel 1
INT
32,767
-32,768…32,767