Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 129

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 115

To enter values from +128…+255, use these conversion formulas:

Desired Decimal Position Value - 256 = Entered Decimal Position
Value.
As an example, for a divisor of 200, 200 - 256 = -56

Desired Gate Interval Value - 256 = Entered Gate Interval Value.
As an example, for a Gate Interval of 200, 200 - 256 = -56

Desired Scalar Value - 256 = Entered Scalar Value.
As an example, for a Scalar of 128, 128 - 256 = -128

1734-VHSC24

1 Channel 15…24V DC Very High-speed Counter

1734-VHSC5

1 Channel 5V DC Very High-speed Counter
Configuration Data

Data Type Default

Value

Valid Data Values

SS Output Control

SS Out 0 Force

SS Out 0 En

SS Out 0 Electronic Fuse

SS Out 0 Diagnostic Speed

SS Out 1 Force

SS Out 1 En

SS Out 1 Electronic Fuse

SS Out 1 Diagnostic Speed

SINT

BIT 0

BIT 1

BIT 2

BIT 3

BIT 4

BIT 5

BIT 6

BIT 7

0

0=Output Off

1=Output Forced On

0=Output Disabled

1=Output Enabled

0=Auto Retry

1=Latch Off

0 < 8 ms Response

1=50 ms Response

0=Output Off

1=Output Forced On

0=Output Disabled

1=Output Enabled

0=Auto Retry

1=Latch Off

0 < 8 ms Response

1=50 ms Response