Publication 1734-UM011D-EN-P - May 2011

128 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference

Transmit Data / Receive Data / Delimiter / Pad Character

Note that 7 data bits allows ASCII Character data values of 0…127, which
RSLogix 5000 software does support in the signed Short Integer data type
SINT (-128…+127 range).

Note that 8 data bits allows ASCII Character data values of 0 to 255.
To enter values from +128…+255, use this conversion formula:

Desired Decimal Value - 256 = Entered Decimal Value.
As an example, for an ASCII Character value of 128,
128 - 256 = -128

1734-232ASC

1 Channel ASCII Interface Module
Configuration Data

Data Type

Default

Value

Valid Data Values

Transmit End Delimiter Mode

SINT

2

0=No End Delimiter

1=Exclude End Delimiter

2=Include End Delimiter

Transmit End Delimiter Character

SINT

13

(0x0d)

Any Valid ASCII Character

(Default is Carr. Return)

Consume String Data Type

SINT

1

0=Array

1=Short String

2=String

Transmit Swap Mode

SINT

0

0=Disabled

1=16-bit Swap Enabled

2=24-bit Swap Enabled

3=32-bit Swap Enabled

DeviceNet Record Header Mode

SINT

0

0=Transmit Handshake

1=Transmit Immediate