102 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference

1734-IE2V

2 Channel Analog Voltage Input
Configuration Data

Data Type Default

Value

Valid Data Values

Low Engineering Channel 0

INT

0

-32,768…32,767

High Engineering Channel 0

INT

10,000 -32,768…32,767

Digital Filter Channel 0

INT

0

0…10,000 ms

Low Alarm Limit Channel 0

INT

500

-32,768…32,767

High Alarm Limit Channel 0

INT

9,500

-32,768…32,767

Low Low Alarm Limit Channel 0

INT

200

-32,768…32,767

High High Alarm Limit Channel 0

INT

9,800

-32,768…32,767

Range Type Channel 0

SINT

2

0=-10…+10V

2=0…10V

Limit Alarm Latch Channel 0

SINT

0

0=No Latching

1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled

1=Alarms Disabled

Low Engineering Channel 1

INT

0

-32,768…32,767

High Engineering Channel 1

INT

10,000 -32,768…32,767

Digital Filter Channel 1

INT

0

0…10,000 ms

Low Alarm Limit Channel 1

INT

500

-32,768…32,767

High Alarm Limit Channel 1

INT

9,500

-32,768…32,767

Low Low Alarm Limit Channel 1

INT

200

-32,768…32,767

High High Alarm Limit Channel 1

INT

9,800

-32,768…32,767

Range Type Channel 1

SINT

2

0=-10…+10V

2=0…10V

Limit Alarm Latch Channel 1

SINT

0

0=No Latching

1=Alarms Latch

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled

1=Alarms Disabled

Notch Filter (Channel 0 & 1)

SINT

2

1=50 Hz

2=60 Hz

4=250 Hz

6=500 Hz

Real-time Sample (Channel 0 & 1)

INT

100

0…10,000 ms