Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 48

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

32 Configure the Adapter for Direct Connection in RSLogix 5000 Software

3. Select the 1734-AENT/A Ethernet adapter from the list, and click OK,

noting that we used these values.

The New Module dialog opens.

Comm Format choices are the following.

None – the adapter makes a direct connection to each of the

modules referenced by the data.

Rack optimization – digital I/O data is collected into a rack image.

This does not include analog or specialty I/O modules.

Listen only - rack optimization – read or verify data only, but does

not control the modules. When you have multiple controllers, one
controller is used to control and the other controllers are used to
monitor.

4. Choose None as Comm Format, because we are making a direct

connection, and click OK.

Because you entered None as the Comm Format, the requested packet
interval (RPI) is disabled.

Name

POINT_IO_Adapter

IP Address

10.88.70.2

Comm Format

None

Chassis Size

3

Electronic Keying

Compatible Keying

Revision

1.1

The Slot field appears grey because the slot is automatically 0 for
the 1734-AENT adapter.

IMPORTANT

The chassis size equals 1 for the adapter plus the number of
POINT I/O modules installed (physically present on the
POINT I/O backplane).