Startup – Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 14

Advertising
background image

12

95-8661

4.2

stArtup

After power has been applied and the warm-up period

is complete, select the UD10 operating mode. To do

this:

1. Access the Main Menu by touching the magnet to

the ENTER/SELECT button. From there, navigate to

the “Mode Select” menu.

2. From the “Mode Select” menu, select and enter the

appropriate operating mode based on the type of

detector being used.

noTe

If using a PIR9400, note that changing the gas
type on the UD10 does not change the gas type at
the PIR9400. This change is made using a switch
located in the PIR9400. Refer to the PIR9400
instruction manual (95-8440) for details.

noTe

If using a C706X detector, navigate to the “Device
Setup” menu and select the appropriate gas type
and unit of measurement.

3. To exit, activate CANCEL/ESCAPE three times to

return to the main display screen.

4. If the detector is replaced with another detector

type, the UD10 will not recognize it until the mode is

changed.

5. If the UD10 Display is in PIR9400 mode and if:

a. The connection between PIR9400 and the UD10

is removed, the UD10 will show a FAULT on the

Gas Screen. When the connection between

PIR9400 and UD10 is restored, the UD10 will

remove the FAULT indication when current

increases beyond 3.6 mA.

b. Someone removes the PIR9400 & connects

a HART enabled Gas Detector, it will not be

recognized by the UD10 Display until the mode

is changed to HART.

RTC

noTe

The UD10 is set at the factory for US Central
Standard time.

To display and set the Real Time Clock and Date for

the UD10:

1. Using the magnet to activate the switches on the

UD10 display, navigate to the RTC menu.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Display Setup

Write Protect
Alarm Setting
Mode Select
HART Option
RTC
Display RS485
Input Loop Cal

RTC

Displayed
Seconds
Minutes
Hours
Day
Month
Year

2. The first item on the RTC screen is “Displayed”.

Y (Yes) or N (NO) is shown to indicate whether

the time and date will be displayed on the main

screen. To change the setting, use the ENTER/

SELECT button to go to the next screen, then use

the PREVIOUS or NExT buttons to toggle between

Y and N. Once the chosen input is selected, use

the ENTER/SELECT button to enter the selection.

Use the CANCEL/ESCAPE button to exit without

changing.

3. Use the same method to set time and date.

Specifically for the GT3000 Transmitter, the RTC for

the transmitter can be synchronized to the RTC of

the display by going through the Main Menu->Device

Setup->RTC-> 1st slot “Sync W/Disp”.

latching Alarms
The high, auxiliary and low alarm relay settings

are programmable and can be set for latching or

non-latching operation. Alarm configuration can be

done using the local display menu or external HART

interface. Latched alarms on the display can be cleared

through the Display Setup > Alarm Setting submenu

using the magnet or external HART interface.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Display Setup

Write Protect
Alarm Setting
Mode Select
HART Option
RTC
Display RS485
Input Loop Cal

Mode Select

HART Device
PIR9400
C706X
505
NTMOS
CGS
Generic Device