Appendix f, Wiring, Menu structure – Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 31

Advertising
background image

F-1

95-8661

4.2

AppenDix f

USINg A HANDHElD HART DEvICE CONNECTED TO THE UD10’S 4-20 mA OUTpUT

(UD10 wITH ANy DETECTOR)

noTe

Refer to the front of this manual for complete information regarding installation, wiring and startup of the UD10.

WirinG

Important

To ensure proper operation of the HART communication system, a power supply with low noise and ripple must
be used. If noise or ripple on the main power source could interfere with the HART function, an isolated power
source is recommended. For additional information, refer to “Power Supply Requirements” in the Wiring section
of this manual.

menu structure

Refer to the following menu tree when using a HART handheld communicator, connected to the UD10’s 4-20 mA

output.

menu HeLp

Status menus only allow the user to view the data.

The Setup menus allow the user to both view and edit the data.

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

UD10

DISPLAY UNIT

D2441

24 VDC

24 VDC

INPUT

4-20 mA

PLC 4-20 mA INPUT CARD

+

+

250-600

OHMS

Notes: Resistor may be external if voltage input card is used.

Sinking resistance at PLC must be 250-600 ohms

for HART communication.

P12

HART Handheld Communicator Connected to the UD10’s 4-20 mA output

Advertising