background image

4.2

95-8661

n-2

UD10

DISPLAY UNIT

MODEL 505 TRANSMITTER

B2475

SIG

RED

SENSOR

WHT

BLK

+

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

NOTES

1. SHIELDED SENSOR WIRING CABLE REQUIRED.

2. GROUND SENSOR WIRE SHIELD AT TRANSMITTER END ONLY.

3. SHIELDS SHOULD BE STRIPPED BACK WITHIN JUNCTION BOXES.

4. P/N 102883-001 TERMINAL CONNECTOR REQUIRED FOR SENSOR CONNECTION

4.

(PROVIDED WITH SENSOR TERMINATION BOX).

5. HOUSINGS MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.

CGS

SENSOR

CONNECT KEYED SENSOR

PLUG TO PIN CONNECTOR

BLK

WHT
RED

instAllAtion

Refer to the Model 505 Instruction Manual (number

95-8472) for complete information regarding proper

installation of the Model 505 with combustible gas

sensor.

orientAtion

The Model 505/CGS must be mounted with the CGS

sensor opening pointing down.

UD10 Wired to Model 505 Transmitter/CGS Sensor Using Sensor Separation Termination box