Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 6

Advertising
background image

4

95-8661

4.2

RElAyS
The display unit has 4 output relays — high alarm, low

alarm, auxiliary alarm, and fault. The relays have form

C (SPDT) contacts. Low, auxiliary and high alarm relay

contacts are selectable for latching or non-latching

operation, as well as normally energized or normally

de-energized (default) coils. During normal operation,

the fault relay is energized.

Important

Direct connection of 120/240 VAC to the
relay terminals inside the UD10 enclosure
is not allowed, since switching relay contacts
can induce electrical noise into the electronic
circuitry, possibly resulting in a false alarm or other
system malfunction. If the application requires
that AC powered equipment be controlled by the
transmitter, the use of externally located relays is
recommended.

External relays, solenoids, motors, or other devices

that can cause inductive transients should be transient

suppressed. Place a diode across the coil for DC

devices. See Figure 2.

Figure 2—Transient Suppression for inductive loads

RELAY

SOLENOIDS

MOTORS

INDUCTION DEVICES

1N4004

TYPICAL

B0179

POSITIVE

NEGATIVE

MOV

HOT

NEUTRAL

120 VOLT – V13OLA10A

220/240 VOLT – V275LA20A

GE

TYPICAL

{ }

+

DCV LOADS

A0179

4-20 mA OUTpUT mODES
The UD10 offers two operating modes for its 4-20 mA

output circuit.

noTe

A minimum output of 1 mA is required for proper
HART communication.

In the Standard (default) Mode, the linear 4-20 mA

output corresponds to 0-100% full scale gas detected at

the sensor, with 3.8 mA indicating calibrate mode, and

3.6 mA or lower indicating a fault condition. This mode

ensures that the current level is always high enough to

support HART communication and must be selected

when using HART communication for fault diagnostics.

In Replicate Mode, the output of the UD10 matches

the output of the connected detector (except for loop

test/trim, response test, calibration, or if the UD10

has an internal fault). This mode can be used with

detectors such as PIR9400 or PIRECL where multiple

current levels below 4 mA are used for fault diagnostic

purposes.

UD10 with model pIRECl
PIRECL supports two fault modes: PIR9400 and Eclipse

mode. PIR9400 fault mode uses fault codes below 1

mA, while Eclipse mode uses no levels below 1 mA. In

the Standard (default) mode, the UD10 programs the

PIRECL for Eclipse fault mode to ensure proper HART

communication in the event of a fault. In the Replicate

mode, the UD10 programs the PIRECL for PIR9400

fault mode.

mODBUS / FIElDBUS COmpATIBIlITy
The UD10 supports RS485 Modbus RTU communi-

cation. See Addendum number 95-8639 for details. A

model with Modbus RS485 or

foundation

Fieldbus

communication (field selectable via jumpers) is also

available.

DEvICE ENClOSURE
The UD10 housing is a 5 port aluminum or stainless steel

explosion-proof junction box with a clear viewing window.

DEvICE DISplAy
The UD10 is provided with a 160 x 100 dot matrix backlit

LCD display. See Figure 1.

During normal operation, the LCD continuously

displays the detected gas level, gas type, and units

of measurement. The real time clock can also be

displayed if desired.

The display shows the following alarm information:
• High gas alarm
• Low gas alarm
• Aux alarm

The display indicates the following fault information:
• Device fault
• Display fault

The UD10 has smart capabilities to allow easy access

to the following information:
• Detector information
• Measurement range
• Alarm setpoints
• Alarm and event logs

For detailed HART menu structure, refer to the appropriate

Appendix.