8661-4.2 (ud10), Instructions flexvu, Explosion-proof universal display unit model ud10 – Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 3

Advertising
background image

INSTRUCTIONS

FlexVu

®

Explosion-Proof

Universal Display Unit

Model UD10

Important

Be sure to read and understand the entire
instruction manual before installing or operating
the gas detection system. This product can be
used with a variety of Det-Tronics gas detectors to
provide early warning of the presence of a toxic or
explosive gas mixture. Proper device installation,
operation, and maintenance is required to ensure
safe and effective operation. If this equipment
is used in a manner not specified in this manual,
safety protection may be impaired.

ApplicAtion

The FlexVu

®

Model UD10 is recommended for

applications that require a gas detector with digital

readout of detected gas levels as well as analog 4-20

mA output with HART, relay contacts, and Modbus

RS485 (

foundation

Fieldbus option available). The

UD10 Universal Display Unit is designed for use with

Det-Tronics gas detectors listed in Table 1.

The display unit is designed and approved as a ‘stand

alone’ device and performs all the functions of a gas

controller.

When furnished with the CGS interface board, the

device can be used only with a CGS sensor for detection

of combustible gas. The UD10/CGS combination is

certified as a “Gas Detector”.

Gas concentration and unit of measurement are

displayed on a digital display. The display unit provides

a linear isolated/non-isolated 4-20 mA DC output signal

(with HART) that corresponds to the detected gas

concentration.

All electronics are enclosed in an explosion-proof

aluminum or stainless steel housing. The display unit is

used with a single detector that may be either coupled

directly to the UD10, or remotely located using a sensor

termination box.

The UD10 features non-intrusive calibration. A magnet

is used to perform calibration as well as to navigate the

UD10’s internal menu.

Description

The UD10 Universal Display can be used with various

4-20 mA gas detection devices, with or without HART.

The unit provides display, output and control capabilities

for the gas detector.

The UD10 utilizes the following I/O:

Signal Inputs: 4-20 mA loop from the sensing device

User Inputs:

Magnetic switches (4) on the display

panel

HART communication (handheld field

communicator or AMS)

foundation

Fieldbus (if selected)

Signal Outputs: 4-20 mA output loop with HART

Modbus RS485 or

foundation

Fieldbus

Three alarm relays and one fault relay

Visible Outputs: Backlit LCD display

HART slave interface via HART

Communicator

4.2

©

Detector Electronics Corporation 2012

Rev: 9/12 95-8661

Advertising