4.2

Device Faults

Description

Recommended Action

EE Fault

Fault in non-volatile memory

Power may have been interrupted while the device

was updating its internal data logs. Recycle

power.

Ref ADC Sat

Sensor signal level is outside the range of the AD

converter

Return to factory.

Active ADC Sat

Sensor signal level is outside the range of the AD

converter

Return to factory.

24V Fault

Problem in 24 volt power supply or power wiring

Check power wiring and output voltage of power

supply.

Flash CRC Fault

Memory fault

Return to factory.

RAM Fault

Fault in volatile memory

Return to factory.

low Voltage

Power supply voltage outside of limits

Check power supply voltage.
Return to factory.

Temp Fault

Temperature sensor fault

Return to factory.

Software Fault

internal software fault

Return to factory.

EE Safety Fault

internal configuration fault

Return to factory.

Gas Under Range

Sensor signal has drifted negative

Device may have been calibrated with background

gas present. Recalibrate the detector. Purge with

clean air if needed.

Sensor Mismatch

Wrong sensor type is installed

Sensor type must match configuration. Change

sensor or configuration.

ADC CnTR Fault

internal hardware fault

Return to factory.

3V Fault

3 volt internal power supply out of tolerance

Return to factory.

Comm Fault

Communication fault

Check detector wiring and power supply.

GEn Fault

Unspecified fault

Verify correct power wiring and supply voltage.

Consult the factory.

12V Fault

12 volt internal power supply out of tolerance

Return to factory.

5V Fault

5 volt internal power supply out of tolerance

Return to factory.

Table 4—Troubleshooting Guide - Device Faults, Continued