Orientation, Calibration – Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 56

Advertising
background image

4.2

K-4

95-8661

orientAtion

The UD10/NTMOS assembly must be mounted

with the detector pointing down (see photo below).

cAlibrAtion

Calibration Notes
The NTMOS detector must be calibrated using 50 ppm

H

2

S in air (never use H

2

S in nitrogen).

Det-Tronics provides two acceptable sources of 50

ppm H

2

S calibration gas for use with NTMOS detectors.

WarnIng

The use of any other H

2

S calibration mixture will

produce inaccurate calibration results, possibly
resulting in a dangerous condition if the detector
under-reports the level of H

2

S.

1. 50 ppm Ampoule Calibration Kit (p/n 007098-005)

with 50 ppm ampoules (p/n 225741-001)

To operate the Ampoule Calibrator:

– Remove the cover and insert a 50 ppm H

2

S

ampoule into the ampoule holder inside the

calibrator. Tighten the thumb screw until snug.

– Place the cover back on the calibrator and

connect it snugly to the NTMOS detector.

– Tighten the thumb screw until the ampoule breaks.
– Rotate the mixing fan by slowly turning the mixing

fan lever.

2. Humidification Tube Calibration Kit (p/n

010272-001) with bottled 50 ppm H

2

S in air (p/n

227117-014). For complete information regarding

use of the Humidification Tube Calibration Kit,

refer to Instruction Manual number 95-8648.

noTe

When calibrating with bottled 50 ppm H

2

S in air,

the humidification tube

must be used.

FLEXVU UD10

NTMOS H2S DETECTOR

AMPOULE CALIBRATOR

THUMB SCREW

MIXING FAN LEVER

Ampoule Calibrator Attached to nTMoS Detector

Advertising