Appendix n, Wiring – Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 69

Advertising
background image

4.2

95-8661

n-1

AppenDix n

UD10 with mODEl 505 TRANSmITTER / CgS SENSOR

noTe

For complete information regarding the Model 505 Transmitter, refer to instruction manual 95-8472.

WirinG

4000

3500

3000

2500

2000

1500

1000

500

0

18

19

20

21

22

23

24

25

26

27

28

29

30

Power Supply Voltage

Dist

ance in f

t.

UD10 with PIRECL/OPECL/Model 505

12
14
16
18

AWG

Wire Size

Notes: Maximum cable length from power source to UD10 is 2000 feet.

Maximum cable length from UD10 to sensor/STB termination box is 2000 feet.

UD10

DISPLAY UNIT

MODEL 505 TRANSMITTER

CGS

SENSOR

B2424

SIG

RED

SENSOR

WHT

BLK

+

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

NOTE UD10 HOUSING MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

UD10 Wired to Model 505 Transmitter/CGS Sensor