J-3

95-8661

4.2

orientAtion

OPECL modules must be affixed to a solid, non-vibrating

structure capable of supporting a minimum of 100 lbs (46

kg), located within the system’s rated separation distance.

See examples below.

In all cases, the maximum movement of the supporting

structure under all anticipated operating conditions must

be no more than ±0.25 degrees. When using a vertical

post, the post should be absolutely stable and without

vibration. Generally, when the post is set into the ground,

the portion below grade should be set in concrete at least

1 meter deep.

cAlibrAtion

To initiate zero calibration of the OPECL from the UD10

Display:

1. Using the magnet to activate the switches on the

UD10 display, navigate to the “Calibration” menu.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Device Calibration

Cal Gas Type
Zero Cal
Span Cal
Cal Date

Calibration

Execute
Abort

2. Activate “Execute” (Enter/Select) to start calibration.

3. The UD10 will display “Waiting for Zero” on the main

display screen, with a solid red LED on the OPECL

housing illuminated.

4. After the calibration is successfully completed, the

UD10 automatically returns to the normal display with

the green LED illuminated on the OPECL housing.

A2306

UD10 mA Output During Calibration

(UD10 with OpECl)

UD10 Display Reading

Standard

mode

Replicate

mode

Waiting for Zero

3.8

2.2

back to normal

4.0

4.0