Opecl transmitter lamp fault condition, Menu structure – Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 51

Advertising
background image

J-4

95-8661

4.2

To initiate zero calibration from the OPECL:

1. Using the magnet, activate the magnetic calibration

switch on the OPECL receiver. See Figure below.

The green LED will turn red.

2. The UD10 will display “Waiting for Zero” on the main

display screen, with a solid red LED on the OPECL

housing illuminated.

3. After the calibration is successfully completed, the

UD10 automatically returns to the normal display with

the green LED illuminated on the OPECL housing.

opecl trAnsmitter lAmp fAult

conDition

If the OPECL system experiences a Transmitter (Tx)

Lamp Fault condition, the UD10 display will not indicate

a fault condition and its output will remain at 4 mA. The

OPECL system is still fully functional and able to detect

gas. If a gas alarm condition should occur, the alarm

condition will override the Tx Lamp Fault condition.

The OPECL system indicates a fault condition by

amber indicator LEDs on both the transmitter and the

receiver.

To verify an OPECL Tx Lamp Fault condition, within the

Menu Structure of the UD10 Display navigate to the

device Fault/Status menu:

The Fault status will indicate Y (Yes). Click on “Fault”

and the Fault menu will identify the fault as a “Lamp

Fault”.

For complete information regarding OPECL fault

indications and operation of the OPECL transmitter

lamps, refer to the OPECL instruction manual, number

95-8556.

menu structure

UD10 with Open patch Eclipse model OpECl
Refer to the following menu when using the UD10’s

LCD display and internal magnetic switches.

When connecting a HART Communicator to the UD10’s

4-20 mA output, refer to the “UD10 HART” menu in

Appendix E.

menu HeLp

Status menus only allow the user to view the data.
The Setup menus allow the user to both view and
edit the data.

location of Receiver’s internal Magnetic Switch

PLACE CALIBRATION MAGNET
HERE TO ACTIVATE INTERNAL
REED SWITCH

A2349

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Device Status

General Info
Fault/Status
Device Info
Sensor Info
History

Fault/Status

Op Mode
Cal State
Fault Y