Menu structure – Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 36

Advertising
background image

G-4

95-8661

4.2

gT3000 wITH OxygEN SENSOR

From gT3000:
1. Using the magnet, activate the magnetic calibration

switch on the GT3000. The green LED turns to

yellow.

2. The device automatically performs the zero

calibration.

The yellow LED on the GT3000 is on continuously.

The UD10 displays “Waiting for Zero” on the main

display screen.

3. When the yellow LED on the GT3000 flashes, the

device automatically performs the span calculation.

If using bottled 20.9% oxygen, apply immediately.

The UD10 displays “Waiting for Span” on the

screen.

4. After successful calibration, the green LED on

the GT3000 is on continuously and the UD10

automatically returns to the normal display.

Remove calibration gas (if used).

From UD10
1. Using the magnet to activate the switches on the

UD10 display, navigate to the Calibration menu.

Main Menu
Process Vars
Display Status
Device Status
Display Setup
Device Setup
Device Cal
Display Test
Device Test

Device Cal

Cal Gas Conc
Calibration
Change Snsr Type

Calibration

Execute
Abort

2. Activate “Execute” (Enter/Select) to start calibration.

3. The UD10 will display “Waiting for Zero” on the

main display screen, with the yellow LED on the

detector housing illuminated continuously. The

device automatically performs the zero calibration.

4. When the UD10 displays “Waiting for Span” on

the screen and the yellow LED on the detector is

flashing, the device automatically performs the span

calculation. If using bottled 20.9% oxygen, apply

immediately.

5. After completion of a successful calibration, the

UD10 automatically returns to the normal mode with

the green LED illuminated on the detector. Remove

calibration gas (if used).

menu structure

UD10 with gT3000 Detector
Refer to the following menu when using the UD10’s

LCD display and internal magnetic switches.

When connecting a HART Communicator to the UD10’s

4-20 mA output, refer to the “UD10 HART” menu in

Appendix E.

menu HeLp

Status menus only allow the user to view the data.
The Setup menus allow the user to both view and
edit the data.

Advertising