19

95-8661

4.2

specificAtions

oPERATinG VolTAGE—

24 Vdc nominal, operating range is 18 to 30 Vdc.

Ripple cannot exceed 0.5 volt P-P.

oPERATinG PoWER—

Standard model, with heater and backlight off:

No alarm:

1.5 watts @ 24 Vdc.

Alarm:

3 watts @ 24 Vdc (20 mA current

loop output, and all 3 alarm relays

energized.)

Backlight on:

0.5 watt additional.

Heater on:

3.5 watts additional.

CGS model:

Add 4 watts with CGS interface

board and CGS sensor installed.

Maximum power in alarm, with heater and backlight on:

7 watts @ 30 Vdc (Standard model)

11 watts @ 30 Vdc (CGS model)

noTe

Heater turns on when the internal temperature
drops below –10°C (default operation). Heater
function can be disabled to save power.

noTe

Appropriate relays will be activated when a fault
or alarm occurs.

CURREnT oUTPUT—

Linear isolated 4-20 mA output with HART.

3.8 mA indicates calibrate mode.

3.6 mA or less indicates a fault condition.

Maximum loop resistance is 600 ohms at 18 to 30 Vdc.

CURREnT oUTPUT RESPonSE TiME—

Toxic gas mode:

T90 ≤5 seconds.

Combustible gas mode:

T90 ≤4 seconds.

Combustible gas - open path mode: T90 ≤4 seconds.

UD10 with CGS:

T90 <12 seconds.

CURREnT oUTPUT ACCURACy—

Toxic gas mode:

<1% error.

Combustible gas mode:

<1% error.

Combustible gas - open path mode: ≤0.01 LFL-m.

UD10 with CGS:

±3% LFL 0-50 range,

±5% LFL 51-100 range.

RElAy ConTACTS—

Three Alarm Relays: Form C, 5 amperes at 30 Vdc.

Selectable energized/de-energized.

Selectable latching or non-latching.

Refer to Table 1 for range and

default settings.

WarnIng

When in non-latching mode, the control device
must latch the alarm output.

One Fault Relay:

Form C, 5 amperes at 30 Vdc.

Normally energized for no fault

condition with power applied.

RElAy RESPonSE TiME—

≤ 2 seconds.

WiRinG TERMinAlS—

14 to 18 AWG wire can be used.

oPERATinG TEMPERATURE—

–55°C to +75°C.

SToRAGE TEMPERATURE—

–55°C to +75°C.

HUMiDiTy RAnGE—

5 to 95% RH (Det-Tronics verified).

ElECTRo-MAGnETiC CoMPATibiliTy—

EMC Directive 2004/108/EC

EN55011 (Emissions)

EN50270 (Immunity)

DiMEnSionS—

See Figures 12 and 13.