Det-Tronics UD10 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 55

Advertising
background image

4.2

K-3

95-8661

NOTE 1

REMOVE UD10 ELECTRONIC MODULE FOR ACCESS

TO NTMOS CONNECTOR BOARD (NO TOOLS REQUIRED).

NOTE 2

GREY AND ORANGE WIRES FOR FACTORY USE ONLY.

NOTE 3

HOUSINGS MUST BE ELECTRICALLY CONNECTED TO

EARTH GROUND.

UD10

DISPLAY UNIT

B2493

J2

P1

COM 1 (GR

A

Y)

COM 2 (OR

ANGE)

C

AL (YELL

O

W)

R

TN (BLA

CK)

4/20 (WHITE)

24V (RED)

SHIELD

CA

L

RT

N

4/20

24V

CONNECT TO UD10 MODULE’S J3 WITH
FACTORY INSTALLED CABLE

NTMOS CONNECTOR BOARD

NTMOS

H2S DETECTOR

RED

BLA

CK

WHITE

YELL

O

W

GREY

OR

ANGE

nTMoS Detector Wired Directly to UD10 via the nTMoS Connector board

(nTMoS Connector board is

Required for HART Communication)

UD10 with nTMoS Connector board Wired to nTMoS Detector with STb Termination box

(nTMoS Connector board is

Required for HART Communication)

NOTE 1

REMOVE UD10 ELECTRONIC MODULE FOR ACCESS

TO NTMOS CONNECTOR BOARD (NO TOOLS REQUIRED).

NOTE 2

GREY AND ORANGE WIRES FOR FACTORY USE ONLY.

NOTE 3

HOUSINGS MUST BE ELECTRICALLY CONNECTED TO

EARTH GROUND.

UD10

DISPLAY UNIT

B2494

J2

P1

COM 1 (GR

A

Y)

COM 2 (OR

ANGE)

C

AL (YELL

O

W)

R

TN (BLA

CK)

4/20 (WHITE)

24V (RED)

SHIELD

CA

L

RT

N

4/20

24V

STB TERMINATION BOX

NTMOS

H2S DETECTOR

RED

BLA

CK

WHITE

YELL

O

W

GREY

OR

ANGE

CONNECT TO UD10 MODULE’S J3 WITH
FACTORY INSTALLED CABLE

NTMOS CONNECTOR BOARD

Advertising